Skip to main content

How to use the Tamper of an AMC in BIS

 AMC Hardware:
Any AMC has an internal tamper switch (micro switch on the board) and an external tamper connector
(Signed with "T" on the housing between Wiegand 3 (or RS-485 3) and RS485EXT). Both contacts are
parallel connected.
So if one contact is opened the state of the other contact doesn't matter because in that case there is already
a tamper alert pending. That means: If the external contact is not used it has to be short-circuit by a short
wire.
If the AMC works fine you can see the messages "SABOTAGE_ALERT" and "SABOTAGE_OK" within the
LAC logging console when switching the tamper switch.
Software:
You only have to create an Association in the BIS Configuration that triggers on the address
AccessEngine.Devices.<AMC 4 name>.Sabotage. The two line conditions are 4062 (Sabotage OK) and
4061 (Sabotage Alarm).


JavaScript errors detected

Please note, these errors can depend on your browser setup.

If this problem persists, please contact our support.