How to connect 4-wire Smoke Detectors to D2000 Series Control Panels.
Connect the 4-wire smoke detector Alarm Loop terminals to any supervised point. Route power through a D133 (or D134) Relay Module using the following connections:
- Relay X1+ to Panel Aux+
- Relay X1- to Panel Ext1
- Relay N/C1 to Panel Aux+
- Relay COMM1 to Smoke Power +
- Smoke Power - to panel Aux -
- Note: When using D134 relays, the connection points X2+ X2-, N/C2, COMM2, etc. can be substituted for or X1+ X1-, N/C1, COMM1, etc.
- The control panel’s external relay output EXT1 must be programmed for the reset function (EXT1 or EXT2).
- Set Relay Logic to Function One Only
- Set Function One to RESET
Resetting the System
- Resetting the system takes about 20 seconds. If points do not reset, contact your alarm company for help. To reset:
- Ensure the system is off (On light is off).
- Press the [3] key. The display shows the following:
- ENTER CODE TO RESET SENSORS
- Enter your passcode (Owner type passcode required). Resetting begins and the display shows the below; this procedure takes about 20 seconds:
- RESETTING...
- After the system resets, the display returns to the off state.