How to Correct All Zone 9 and up reporting to the CS as Zone 1 7000, 9000, G, GV2 & GV3 Panels

Issue

Central Station receiver receives an alarm zn 1 when any point 9 and higher is faulted/tripped.
 
Solution
 

Panel is programmed to send BFSK format. In point assignment programming, under the BFSK/Relay perameter there is a value of 1programmed at zone 15 which send a BFSK report of 1 to central station.

Part numbers D7212B, D9112B, D7212B1, D9112B1, D7212, D7412, D9112, D9124, D9412, D7212G, D7412G, D9124G, D9412G, D7212GV2, D7412GV2, D9124GV2, D9412GV2, D7212GV3, D7412GV3, D9412GV3,