Skip to main content

How to determine D1255RB, D1256RB and D1257RB compatibility with G-Series control panels.

  •  The D1255RB, D1256RB and D1257RB command centers are compatible with G-Series control panels with firmware revision 7.04 or higher.
  • When connected to earlier revision panels, the keypad basic functions will operate correctly but LED's for Fire, Silenced, Supervisory and Trouble will not operate correctly.
  • Additionally, the D1255RB, D1256RB and D1257RB keypads are not UL listed with control panels prior to revision 7.04.