How To: Determine the cause of the Contact ID signal of a 310

If sending contact-ID, measure voltage between terminals 1 and 8, the normal voltage should be between 4.5vDC and 7.5vDC, anything higher or lower is a ground fault condition. Keep measuring voltage while taking the wires off terminals one at a time until you see normal voltage return