Skip to main content

How to determine why the keypad displays trouble but does not indicate any point troubles

To check the history of the control panel enter the Master pin and enter # 89. If the system shows a SYSTEM FAULT 04, follow the steps below:   

Solution: Start by disconnecting the field wiring from each terminal while watching the keypad display. The keypad power light should stop flashing when the ground fault is removed.  

If a keypad is not present at the control panel, use a voltmeter to find the ground fault:

Connect the negative lead to terminal 1 or 2 panel ground.

Connect the positive lead to terminal 8 AUX Power.

Voltmeter should read between 6.5 VDC and 7.5 VDC. A reading that is higher or lower indicates a ground fault.  

Remove the field wiring from the control panel while watching the voltmeter. When the voltage returns to the normal voltage of 6 .5 VDC to 7.5 VDC, you have found the wire that is causing the ground fault.

 