Skip to main content

How to Diagnose Point 74 Faulted When Using FA113 Keychain Remote Control

Issue

Why does system state that point 74, a wireless keyfob, is faulted?

Solution

This is a known function of the 9000 series panels. The keyfob occupies point 74 when programmed. As a result, the point will remain violated if the keyfob is used to arm the system and the code entered at the command center to disarm the system. A workaround would be to disarm the panel using the keyfob if it is used to arm the system.

Part numbers FA113, FA400, D8125INV, D7412G, D9412G, D7412GV2, D9412GV2, D7412GV3, D9412GV3, D7412GV4, D9412GV4, B600, B8512G, B9512G