How to interpret panel reports generated by MISSING Point Events on G Series Panels.

Missing Point Reports occur if a point which has been enabled in the panel programming, is not seen by the panel.  The type of report will depend on the type of point.
  • Fire points generate missing trouble responses.
  • Non-fire 24-hour points generate missing alarm responses.
  • Non-fire, non 24-hour points generate missing alarm responses while armed, and trouble responses while disarmed. EXCEPTION: Non-fire, non 24-hour points with a point response of 9 to D generate a missing alarm response while disarmed.