Issue

How far can I mount the D1260 from the panel?
 
Solution
 
The recommended distance is no more than 2000 feet from the control. However, the total wire resistance should not exceed 14ohms. 18 guage wire is recommended.
 
Part numbers D7212B, D9112B, D7212B1, D9112B1, D7212, D7412, D9112, D9124, D9412, D7412G, D7412G, D9124G, D9412G, D7412GV2, D7412GV2, D9124GV2, D9412GV2, D7412GV3,D7412GV3, D9412GV3, D7412GV4, D7412GV4, D9412GV4, B8512G, B9512G, D1260