How to set the supervision time for individual points.

  • Starting with the GV4 series panels, supervision time can be selected for individual points rather then depend on a 'system supervision time'. This is particularly useful when points will be out of range of the receiver for an expected duration of time, or for bill traps, panic buttons or other devices which might be stored in a safe or could be removed from the site.

    Wireless point supervision can be set for individual points using point index settings with the GV4 panel and B820 wireless interface.

  • Using the Wireless Point Supervision Time parameter in the point index, select the supervision time for wireless points following the selected point index, as described below.

  • Selections: None, 4 hours, 12 hours, 24 hours, 48 hours or 72 hours. On previous version panels this selection was made while programming the wireless interface device, such as the ISW-D8125CW-V2.

Wirless Supervision Time.png

  • EN4200,B820