Skip to main content

How to troubleshoot Popit points displaying Faulted even with EOL across the loop contacts?

This article is for troubleshooting a popit point which shows faulted even when a 33k end of line resistor is strapped across the loop terminals.

When two Popits are addressed with the same dip-switch setting, the panel sees the address as Faulted regardless that an end-of-line resistor is connected across the loop input. Use the following steps to troubleshoot.

  1. Verify the point is programmed correctly with Source= Popex when using the B299, or Zonex if using the D8125.
  2. Change the popit dip-switch address by temporarily flipping the 0 switch. If the 0 switch is on, turn it off or vice versa. Alternatively, disconnect the correctly addressed popit and reconnect the Zonex loop wires to continue the loop.
  3. Use View Point Status to check the state of the point (see the article; How to use View Point Status).
    1. If the point state changed from Faulted to Normal, then there is another popit in the system with the same address as the one which was disconnected.
    2. If the point state changed from Faulted to Missing, then another issue in the loop is causing the disconnected point to go missing. See How to troubleshoot popit loops.
  4. Isolate the duplicate addressed popit with the following steps.
    1. Remove the correctly addressed popit from the loop or change the popit address by temporarily flipping the 0 switch. If the 0 switch is on, turn it off or vice versa. View Point Status should still show the address as Normal.
    2. Half split the popit loop until the address goes missing. Continue half splitting to isolate the duplicate addressed popit.



JavaScript errors detected

Please note, these errors can depend on your browser setup.

If this problem persists, please contact our support.