B-Series Battery discharge and recharge schedule
Discharge Cycle
|
AC Off
|
AC Fail Report when programmed.
|
13.65 VDC
|
Charging float level.
|
12.1 VDC
|
Low Battery Report sent if programmed.
|
10.2 VDC
|
Minimum operational voltage. Keypads display low battery
Messages.
|
Recharge Cycle
|
AC On
|
Load shed relay reset; battery charging begins; Battery Trouble and AC Restoral Reports sent.
|
13.4 V
|
Battery Restoral Report sent. Battery float charged.
|