Connect smoke detectors to any supervised panel point. Using a suitable power supervision device according to manufacturers instructions, route power to smokes using a form C relay such as the Bosch D133 or D134, as follows:
-
D2212 EXT1 to D133/D134 X1-
-
D2212 Aux Power+ to D133/D134 X1+
-
D133/D134 Comm 1 to 4 wire smoke detector (-)
-
D133/D134 N/C 1 to 4 wire smoke detector (+)
Program 2212 handler as follows:
Relay 1
-
Logic= Function 1 Only
-
Function 1= Reset