View Point Status is an important part of troubleshooting which is used to determine the current state of input points. For example, when the panel annunciates a point trouble, view point status will display if the point is missing or faulted in an open or short state.
B9512G/B8512G and B-Panels:
-
Press [Menu] + [2] + [2].
-
Press ENT. The keypad displays AREA X ## (where X ## = the area number and the number of points to view).
-
Press Next to advance point by point. The point number, point text and point state displays.
-
Press ESC to return to the area’s idle text.
D7212/D7412/D9412/G-GV4:
-
Ensure the command center is at idle text.
-
Press the ESC/MENU key to enter the command menu. Press NEXT until the VIEW PT STATUS function displays.
-
Press ENT. The keypad displays AREA X ## (where X ## = the area number and the number of points to view).
-
Press ENT. The keypad displays PT ## XXXXX (where XXXXX = the type of point). Press ENT again to see the point state.
-
Continue to press ENT to see the type and condition of each point.
-
Press ESC to return to the area’s idle text.
Some possible troubleshooting solutions:
-
The Trouble condition may be due to incorrect programming. For example, a Normally Closed door, where opening the door generates a trouble condition. Consider selecting a point response for Trouble on Short to annunciate shorted wiring. Or one which doesn’t generate any trouble condition at all.
-
PT###-SHORT. This usually indicates a lower-than-normal voltage across the end-of-line resistor. This may be due to incorrect wiring of the end-of-line resistor (wired in parallel vs series). The point will show ‘short’ whenever the protection device is normal. It may also indicate a misconfigured or faulty expansion device. D8128D with an incorrect dipswitch setting (refer to the D8128D IOG). Two D9127 popits sharing the same dip-switch address while both are in a normal state.
-
PT###-OPEN. This usually indicates a higher-than-normal voltage across the end-of-line resistor. This may be due to incorrect wiring of the end-of-line resistor (wired in series vs parallel). The point will show ‘open’ whenever the protection device is normal. It may also indicate a broken wire, damaged contact or motion detector, or a misconfigured/faulty expansion device.
-
PT###-MISNG. This indicates the panel cannot see the point. This may be due to a programming error (such as incorrect point source selection), wiring problem or misconfigured/faulty expansion device.