How to determine which points are available for programming using the D8125MUX.


 


  • D9412,G-GV4 panel types:  Addresses 9 to 127 on Zonex 1 and Points/Addresses 129 to 247 on Zonex 2 for the control panel.

  • D7412,G-GV4 panel types:  Addresses 9 to 75 on Zonex 1of the D7412/G/GV2 control panel.

  • D7212,G-GV4 panel types:  Points/Addresses 9 to 40 on Zonex 1.

Note: Points/Addresses 129 to 247 are physically addressed as Points 9 to 127 and programmed as 9 to 127 in the D8125MUX with the D5060 programmer.  Points added as 9-127 and added to Zonex 2 convert to points 129-247 by the panel.  The control panel adds 120 to the address of points connected to Zonex 2 when it displays them on the keypad and reports to the central station.

Points are converted for use on Zonex 2 as follows: