How to configure the B8512G or B9512G to test panel phone lines every 6 hours for NFPA 72 – 2013.


NFPA 72 – 2013 introduced changes from the previous code requirements for supervising phone lines.

  • The requirement for phone supervision time increases from 5 minutes to 60 minutes.

  • The requirement for annunciating the failure of either phone line is changed to 6 hours.

Proper phone line supervision is accomplished with 4 schedules with one every 6 hours each day. This provides annunciation at the monitoring station within 6 hours of a failure on either phone line.

The below example describes using 4 schedules, 6 hours apart at 01:00, 07:00, 13:00 and 20:00.

  1. In Panel Wide Parameters > Phone and Phone Parameters, set Two Phone Lines =YES. Figure 1: Set Two Phone Lines=YES

  2. Create 4 skeds 6 hours apart (see figure 2), each configured with Function= Send Test Report. Select the following options In the Function area of each Sked (see figure 3).

    1. Parameter1: Deferred=NO.

    2. Parameter2: Frequency=Scheduled.

    3. Parameter3= Custom.

    4. Parameter4= RG 1, Primary and RG 1, Backup 1 both selected.

    5. https://community.boschsecurity.com/t5/image/serverpage/image-id/27435i8685FECD073F19B5/image-dimensions/358x278?v=v2 Figure 2 Skeds 1 - 4

    6. Figure 2:  Skeds 1 - 4
    7. https://community.boschsecurity.com/t5/image/serverpage/image-id/27436i70F639CB95219B93/image-dimensions/378x322?v=v2

    8. Figure 3: Sked function settings for Skeds 1 – 4

 

NFPA 72 – 2010

  1. 26.6.3.1.4.1 Single Communications Technology.

    • Where only one communications technology is used, any failure of the communications path shall be annunciated at the supervising station within 5 minutes of the failure.

  2. 26.6.3.1.4.2 Multiple Communications Technologies.

    • Where two or more different technologies are used, the following requirements shall be met:

    • Provision shall be made to monitor the integrity of each communications path.

    • Failure of any communications path shall be annunciated at the supervising station and at the protected premises within not more than 24 hours of the failure.

    • Exception: Where technologies used are described elsewhere in this Code, monitoring for integrity shall be permitted to comply with those requirements.

 

NFPA 72 – 2013

  1. 26.6.3.1.5 Single Communications Path.

    • Unless prohibited by the enforcing authority, governing laws, codes, or standards, a single transmission path shall be permitted, and the path shall be supervised at an interval of not more than 60 minutes. A failure of the path shall be annunciated at the supervising station within not more than 60 minutes. The failure to complete a signal transmission shall be annunciated at the protected premises in accordance with Section 10.15.

  2. 26.6.3.1.6 Multiple Communications Paths.

    • If multiple transmission paths are used, the following requirements shall be met:

    • Each path shall be supervised within not more than 6 hours.

    • The failure of any path of a multipath system shall be annunciated at the supervising station within not more than 6 hours.

    • The failure to complete a signal transmission shall be annunciated at the protected premises in accordance with Section 10.15.

  3. 26.6.3.1.7* Single Technology.

    • A single technology shall be permitted to be used to create the multiple paths provided the requirements of 26.6.3.1.6 (1) through 26.6.3.1.6(3).