Issue
-
Trouble connecting to the D4412 with RPS / RAM IV using the DX4010i.
-
What dip switches need to be set to make the DX4010i connect to the panel?
-
What type of cable is needed between the DX4010i and the Laptop or PC?
Solution
-
RAMIV / RPS needs to be revision 3.6 or higher.
-
Set the address 0 (Installer's mode) Dip Switches 6 and 8 in the off postion on the DX4010i.
-
Use a NULL cable to connect the DX4010i to the Laptop or PC.
-
For remote programming connection, use the RJ-16 to molex connector to the Aux / Data header.
-
Lock the Installer or Reset Pin on the panel.
-
In the RSP/ RAMIV Connection screen change the connection type from MODEM to ENHANCED DIRECT, then click connect.
*If connected to a D4412 panel and the address is set wrong on the DX4010i then a message of "INVALID RAM PASSCODE" may be generated.