How to Reset Power on the D6112, D4112


 There are two ways to have resettable power.

  1. Resetting smokes when powered from the panel.

  • Connect the negative wire from the smokes to terminal 14.

  • Connect the positive wire from the smokes to terminal 15.

  • Command 47 will reset the power on the smokes.

   Resetting smokes when powered from an external power supply.

  • Must have a D136 relay in the AUX relay slot (three pins up, left side justified)

  • Power for the smokes will go through terminals 8-9 (NC contacts)

  • Program prompt 1.17 for the amount of time for the relay to open(5,10 sec)

  • Combo group 4 enter a 7,  account1 and account2 are set to "no"

  •  A 47 ENT at the keypad will now activate the ondoard relay for the set time, dropping power to the 4 wire smokes