How to Plan Onboard Zone of the D6112


Issue

How many on-board zones does the D6112 Control Communicator have?

Solution

The D6112 Control communicator has eight end-of-line resistor supervised hardwire protective zones. There are six standard programmable zones; one nominal 12 VDC powered zone optimized for two-wire smoke detectors and one nominal 12 VDC powered zone optimized for two-wire glass-break detectors.