How to program the panels for AC fail report and AC restoral reports


 AC Fail/Res Rpt

Default: No

Selections: Yes/No

Parameter Description:  AC Power Supervision reports are sent to the central station and local printer at the time programmed for AC Fail Time.

IMPORTANT: To comply with NFPA standards and UL 864 requirements for Commercial Fire Systems, program this item NO and program AC Tag Along as YES.

Parameter Options

  • Yes: Send AC Fail and AC Restoral reports.

  • No: Do not send AC Fail and AC Restoral reports.

Programming Instructions

D5200 Programming

1) Receive copy of 9000MAIN

2) Enter group PANEL WIDE PARAMETER

3) Enter group Power Supervision

4) Fail/Res Rpt   Yes/No   (SPACE bar to change)

*Must press ENTER for each prompt entry

5) Send Load to panel