How to test the RF280THS wireless smoke used on the D4412 and D6412.


  • Canned smoke must be used to test the RF280THS and generate a panel alarm.

  • After the RF280THS test button is pressed, View Point Status will reflect the point state as changed however a panel alarm will not be generated.

  • Simulate an alarm following the instructions for an Underwrites Laboratories, Inc. (UL) Listed aerosol smoke detector tester, such as the Home Safeguard Industries' 25S.