How to troubleshoot missing onboard points 1-8 on the D4412/D6412.


  • Verify points are programmed as 'onboard' points.  If programmed as an expanded device which is not added to the panel the point(s) will show as missing.

  • In keypad programming, verify nibbles 0706, 0711, 0716, 0721, 0726, 0731, 0736, 0741 are programmed as 1. Other options would indicate either an expansion device or disabled.

  • Using RPS, verify the device is set to On Board in Point Configuration.  Other settings would cause a point intended to be used on board to show missing.