B-Series Battery discharge and recharge schedule
|
Discharge Cycle |
|
|
AC Off |
AC Fail Report when programmed. |
|
13.65 VDC |
Charging float level. |
|
12.1 VDC |
Low Battery Report sent if programmed. |
|
10.2 VDC |
Minimum operational voltage. Keypads display low battery Messages. |
|
Recharge Cycle |
|
|
AC On |
Load shed relay reset; battery charging begins; Battery Trouble and AC Restoral Reports sent. |
|
13.4 V |
Battery Restoral Report sent. Battery float charged. |