Where is DRILL authority configured for B925F or B926F keypads?

Question

Where is DRILL authority configured for B925F or B926F keypads?

Answer

DRILL authority is configured in the settings for Walk Test All Fire Points.

Operation

When DRILL is pressed for 3 seconds the keypad asks for a passcode. Fire Drill starts when the correct passcode is entered.

  • Passcode requirement:

    • User Configuration à User (Keypad) Functions à Walk Test All Fire Points

      • [P] Passcode required.

      • [E] Passcode not required.

      • [ - ] Function disabled.

    • User authority:

      • User Configuration à Authority Levels à Walk Test All Fire Points.

The following occurs when a passcode with correct authority is pressed.

  • The control panel sends a FIRE DRILL START report to the central station receiver.

  • The Fire Bell/Fire MNS/Fire Drill output activates until a user ends the drill by silencing the Fire Bell/Fire MNS/Fire Drill.

  • Fire points, gas points and MNS points are active. An alarm on a fire point, gas point or MNS point ends the drill. The control panel sends Fire Alarm/Gas Alarm/MNS point reports.

  • When the fire drill ends, the control panel sends a FIRE DRILL END report.

B925F Keypad (left) and B926F Keypad (right)